NHGFFD001

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD20
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHGFFD002

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHGFFD003

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHGFFD004

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHGFFD005

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD60
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Not Applicable
Fire glass fitted
Not Applicable
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHGFFD015

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Not Applicable
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL1FD008

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL1FD007

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL1FD006

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL2FD011

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL2FD010

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL2FD009

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL3FD014

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL3FD013

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
NHL3FD012

Last Inspection *Remedial

Last Inspection

07/01/26
07/04/26

Next Safety Check

Fire Door Rating
FD30
Repair Risk Assessment
Notes on Remedial Repairs or Deviations
Door closes properly
Yes
Are there gaps around the door over 4mm?
No
Intumescent strip fitted & free from damage
Yes
Notes on Remedial Repairs or Deviations
Fire door keep shut sign installed
Yes
Fire glass fitted
Yes
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations
Damage to fire door
No
Inspection Result
Passed
Notes on Remedial Repairs or Deviations
Notes on Remedial Repairs or Deviations